(See 'download.jpg' file attachment)We have seen instances where improper jumper settings on the CPU board from the manufacturer will cause this to occur. Please contact ProSoft Technical Support for further details. Phone: (661)716-5100Email: support@psft.comYou can ...
Lire la suiteYes, the following information outlines the protection on the Prolinx The Serial Port ProtectionRS485/422 port interface lines TVS diode protected at +/- 26.7V breakdown voltage and +/- 24V stand-off voltage.RS232 port interface lines fault protected to +/- 36V pow...
Lire la suiteThe ACT LED on the ProLinx gateway is hardwired to the TXD signal of the serial line. If this LED comes on solid when the serial cable is plugged in, that is telling you that there is a constant "Transmit" happening on the serial port. Disconnecting the cabl...
Lire la suiteMost ProSoft products which either go in a Rockwell PLC rack (InRAx modules) or communicate over EtherNet/IP (EIP), most of these products do not require an .EDS file for proper operation. Because of this. we do not provide .EDS files for every product which could support them. ...