Connect PC to module's debug / configuration port using a null-modem cable Start Hyperterminal, Putty or other comm program and use the following settings: bits per second: 57,600 data bits: 8 parity: none stop bits: 1 flow control: Xon/Xoff Once connected, press &quo...
Lire la suiteYou need to use the serial port on a SLC505 to talk to 3 devices. Two of them are ulogix over radio modems using DF1 protocol. The 3rd is a medina telemetry unit which supports DF1 point-to-point only. You would be able to use a 4102-MCM4-DFCM4 module. This module will support 4 ...
Lire la suiteThe 4xxx and 5xxx series ProLinx Gateways have opto-isolated application serial ports. The debug/config serial port is not opto-isolated. The opto-isolators used on ProLinx are the HCPL-0531 type from Avago Semiconductor and are UL recognized to withstand 2500 Vrms (input to outp...
Lire la suiteHow can I connect more than one DF1 device to an Allen-Bradley processor's channel 0 port. You will need to use the serial port on a SLC505 to talk to 3 devices. Two of them are MicroLogix over radio modems. The 3rd is a medina telemetry unit which supports DF1 point-to-point onl...
Lire la suiteAll ProLinx modules with DFCM driver have no menu display on hyperterminal when pressing '?' key. Cannot access debug port. The DF1 pass-through port parameter is set to yes in the configuration file. Reconfiguring the debug port: Open the .cfg file using Microsoft Notepad For...
Lire la suiteProSoft makes a DF1 gateway that functions as a multiplexor. This permits up to 3 DF1 master devices to communicate to a single SLC or MicroLogix processor while only using a single communication port on the processor. Additional information can be found on the produc...
Lire la suiteThe 4101 module has two serial ports. Each port is used for protocol communications. To access the debug menu, one of the serial ports needs to be placed in debug mode. Follow these steps to access the debug menu: Connect to the port you wish to view the debug menu on. Reboot ...
Lire la suiteFor this type of application, your customer can use the ProLinx gateway. This gateway is a multiplexer between one slave DF1 device and 3 master devices. You will have to connect the SLC505 serial port to the master port of the ProLinx and use the 3 others ports to connect the 2 ...
Lire la suiteThis is a normal error on a ProLinx module which does not have an Ethernet board. The base program of the ProLinx module will try to load the Ethernet driver. If there is no Ethernet hardware on the ProLinx module, the error message will be generated, and the module will then sta...
Lire la suiteTechnical note from Rockwell Automation that can be used to set this up:The SLC 5/04 has a DF1 to DH+ pass thru option that can be set in the processor that will allow a DF1 connection from the ProLinx with the pass thru set to see the DH+ networkRelated Keywords:typical connecti...
Lire la suiteIt is recommended to use ProSoft Configuration Builder to upload and download configuration files to 4xxx and 5xxx series gateways. ProSoft Configuration Builder is provided free of charge and can be downloaded here: http://www.prosoft-technology.com/Products/ProSoft-Softwa...
Lire la suiteThe only way to configure or debug a 4xxx or 5xxx series ProLinx gateway is through the serial Debug/Config port. ...
Lire la suiteAll 4xxx and 5xxx AB Remote I/O gateways function as Remote I/O Adapters. These gateways support a single BTR and a single BTW. It is possible to configure rack address, and as 1/4, 1/2, 3/4, or full rack.If an Allen-Bradley Remote I/O Scanner is needed, or if you are upgrading a...
Lire la suiteWhen using Sycon software with a PDPM module, you will see a "bad assignment" in the network view menu. This does not indicate an error with the PDPM module communicating to the slave. Sycon software is a generic PROFIBUS master software that is used in many master appl...
Lire la suiteAll 4000 and 5000 series gateways follow the attached document to set the time and date. The time/date is often used for web applications, as well as being used for IEC101M, 103M, and DNPM applications. ...
Lire la suiteWhen using a ProLinx gateway that supports DF1 pass-through, you willneed to enable at least one command on DFCM port 0. If no commands are really needed, than the poll rate on a single command can be set to a high poll rate in order to minimize the impact....
Lire la suiteRefer to the following article, however, on the MicroLogix series of processors, you MUST use the CPW command instead of the COP command....
Lire la suiteThe "delay preset" refers to the number of processor scan counts waited until that data map entry is updated.It is recommended to set the preset to 1000 to begin with in order to avoid a condition where the processor will spend most of its time updating the data map and...
Lire la suiteThe Prolinx and PLX series communication gateways require the following power supply: 24VDC at 500MA ...
Lire la suiteThe user will get this error if the revision of the module firmware is newer than that in the utility's database. If there were no changes to the config this will not pose a problem for the user.ProLinx ProLinx configuration tool...
Lire la suitePlease note that modscan32 does not support embedded modbus messages in a TCP/IP packet. Modscan32 uses MBAP messaging, which is what the ProLinx driver uses on port 502. In order to use port 2001, and have that data pass-thru to port 0 modbus master port, you'll need a software ...
Lire la suiteSelecting and confirming from the module menu just prepares the module to receive a configuration file. To actually accomplish the configuration file download, you must select send file from the transfer menu in hyperterminal, browse to the filename.cfg file, select it, pick the ...
Lire la suiteThe Wonderware driver ABKF2 does not process or use the station ID when operating in Full Duplex mode. The DF1 full duplex specification requires a station id when more than one device is present on a network.A workaround has been implemented in our DF1 implementation. ...
Lire la suiteThese gateways have a total of 4 serial ports. Each of the 4 ports can be independently configured for either serial Modbus (Modbus RTU) or DF1....
Lire la suiteIn 4xxx PDPS Gateways: The data movement in the PROFIBUS Slave module (PDPS) is as follows: Input registers (0 - 99) move from the PROFIBUS Slave module to the PROFIBUS Master.Output registers (100 - 199) move from the PROFIBUS Master to the PROFIBUS Slave module.In 5xxx PDPS Gat...
Lire la suiteThe dimensions for the 5000 series ProLinx module are: ProLinx Plus (aluminum enclosure) standard 5.20h x 2.07w x 4.52d inches 13.2cmh x 5.25cmw x 11.48cmdextended 5.20h x 2.73w x 4.52d inches...
Lire la suiteAll ProSoft gateways and In-Chassis modules contain a database that is based upon 16 bit words. To store 32 bit data types 2 consecutive registers or elements are required.Examples of these 32 bit data types are REAL, FLOAT and DINT's also known as double Integers.To access...
Lire la suiteThe following document outlines the ProSoft implementation of the IEC-60870-5-104 Server communication module as pertains to all -104S products. ...
Lire la suiteThe ACT LED is hardware driven by the TXD signal of the PC connected to it. There is an issue with some Dell latitude laptops where the DC powersupply causes the TXD signal to go active. During this state, ProSoft Configuration Builder,hyperterminal, and other serial communicatio...
Lire la suite