Since RSLogix uses signed integers, the highest positive value that can be entered is 32767. 

To avoid this issue, when specifying higher baud rates, Prosoftmodules only require the first 3 digits of the baud rate. e.g., to enter a baud rate of 38400, enter 384. Use 576 for 57600, and 115for 115200.