MVI56-MNETC module would lock up and stop communications on the Modbus TCP/IP side. Version 1.02 of the MVI56-MNETC added a parameter to the configuration file that will allow the user to set ... Bulletin 1-6446251 MVI56-MNETC locking up on the TCP/IP side.
Lire la suiteVersion 1.26 of the MVI56-MCM module firmware has been created to address this issue. This new version of code uses interrupt timing, to drop the RTS line as quick as possible, and enable the module ... Bulletin 1-5165141 MVI56-MCM getting intermittent communications errors when operating on both ports
Lire la suiteto 0dB. The solution is to load an earlier firmware version, 1.011; or, upgrade to firmware versions later than 2.073, once they become available. You can find version 1.011 or newer versions
Lire la suite". This parameter sets the "Highest Station Address" with which the PDPMV1 will try to communicate. If this value is set too low, below the Node Addresses of some of the nodes on the network, then those nodes ... I can't get my ProSoft PROFIBUS DP V1 Master to talk to all of the Slave Nodes on my PROFIBUS network. What might the problem be?
Lire la suiteMVI46 Ethernet modules updated from firmware revision 1.02 to 1.03 in 11/2004, ECN 572 addressed an issue that was discovered with all Ethernet versions of the MVI46 module. There was a timing issue ... What is the difference on the MVI46 module from F/W revision 1.02 to 1.03?
Lire la suite