The A-DH485R/B DH485 Router provides intelligent data routing between EtherNet/IP™ and DH485, simplifying the migration from MicroLogix and SLC systems with DH485 communications to EtherNet/IP based ControlLogix or CompactLogix platforms.
The module can be used for remote programming of a SLC5/03 controller via Ethernet.
The DH485 Router’s AIC Mode provides direct conversion between RS485 and RS232, an ideal replacement for Rockwell’s 1761-NET-AIC module.Alternatively, the module makes use of the DH485 destination Node Address, (and Data File address in certain modes), to determine the target Logix controller. The mapping table, which can be configured in minutes, supports connections up to 8 Logix controllers.
In Transparent PCCC mode, the user will be able to program and connect to SLC5/03 PLCs.
The module can operate in both Logix “owned” and standalone mode. With a Logix connection, the input and output assemblies will provide additional diagnostics information in the Logix controller environment.The module’s RS485 port uses a terminal block for convenient installation.A built-in webserver provides detailed diagnostics of system configuration and operation, including the display of received DH485 communication packets, without the need for any additional software.
The Slate Configuration Utility software is used for configuration and troubleshooting of the Router. The stand-alone configuration utility allows users to define the setup and configuration of the Router, and connections with controllers and devices.
EtherNet/IP Network
Specification |
Rating |
Connector |
RJ45 |
Conductors |
CAT5 STP/UTP |
ARP Connections |
Max 40 |
TCP Connections |
Max 40 |
CIP Connections |
Max 10 |
Communication Rate |
10/100 Mbps |
Duplex Mode |
Full / Half |
Auto-MDIX Support |
Yes |
Controller Support |
ControlLogix, CompactLogix, MicroLogix, SLC |
Embedded Switch |
Yes, 2x Ethernet ports |
Serial Ports (RS232, RS485)
Specification |
Rating |
Connector |
9-way terminal (shared) |
Conductor |
24 to 18 AWG |
Electrical Isolation (RS232) |
1000 V DC |
Electrical Isolation (RS485) |
1500 Vrms (1 minute) |
Baud Rate (bps) |
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 |
Parity |
None, Even, Odd |
Data, Stop Bits |
8, 1 |
Error Detection |
CRC |
DH485 Router
Specification |
Rating |
Transparent Mode Mapping |
Max. 20 |
Logix Tag Mode Mapping |
Max. 20 |
Reactive/Scheduled Tag Mode Message Support |
PLC-5 Type: Read, Write |
Rockwell Automation Controller programming Support |
SLC5xx range |
Specification |
Rating |
Power Supply |
Input: 10 to 32 VDC, (67 mA @ 24VDC) |
Voltage Fluctuations |
Voltage fluctuations < ±10% |
Power Consumption |
1.7W, 173mA maximum |
Dimensions (H x W x D) |
149.0 x 34.0 x 116.0 mm |
Connector |
3-way terminal |
Conductors |
24 to 18 AWG |
Enclosure Rating |
IP20, NEMA/UL Open Type, Indoor-use only |
Temperature |
-20 to 70 °C |
Relative Humidity |
5 to 90% RH, non-condensing |
Pollution Degree |
2 |
Altitude |
< 2000m |
Earth Connection |
Yes, terminal based |
Emissions |
IEC61000-6-4 |
ESD Immunity |
EN 61000-4-2 |
Radiated RF Immunity |
IEC 61000-4-3 |
EFT/B Immunity |
IEC 61000-4-4 |
Surge Immunity |
IEC 61000-4-5 |
Conducted RF Immunity |
IEC 61000-4-6 |
UL/cUL; Class1, Div 2 | 238,99 kB | Dernière Modification 25/01/2024 |
ODVA Certification | 37,47 kB | Dernière Modification 25/01/2024 |
CE Declaration of Conformity (CE, UKCA, RoHS, UL) | 339,65 kB | Dernière Modification 26/01/2024 |