ProSoft Technology’s EtherNet/IP™ to Siemens® Industrial Ethernet communication gateway allows high-speed bi-directional data transfers between Rockwell Automation® PACs and Siemens® S7 PACs. Two separate Ethernet ports allow each protocol to reside on separate subnets, allowing you to pass data between the two subnets without changing each device’s IP address.
In addition, the gateway includes an embedded EDS Add-On Profile, allowing for simplified integration and reduced commissioning time.
EtherNet/IP™ Specifications
Specification |
Description |
Number of Class 3 Server Connections |
5 |
Supported PLC Types |
PLC2, PLC5, SLC, CLX, CMPLX, MICROLX |
Supported Message Types |
PCCC and CIP |
Class 3 Client Connections |
Connected: 2 |
Number of Class 1 I/O Connections |
2 |
I/O connection sizes |
248/248 |
Max RPI time |
5 ms per connection |
CIP Services Supported |
0x4C - CIP Data Table Read |
Command List |
Support for 100 commands per Client, each configurable for command type, IP address, register to/from addressing and word/bit count. |
Command Sets |
PLC-2/PLC-3/PLC5 Basic Command Set |
Siemens® Industrial Ethernet Specifications
Specification |
Description |
Supported PLC Data Exchange (Read and Write) |
Siemens S7-200, S7-300, S7-400, S7-1200, S7-1500 |
Supported Register Types |
DB, Inputs, Outputs, Flags, Counters, Timers |
Supported Clients |
20 |
Specification |
Description |
Power Supply |
24 VDC nominal 10 to 36 VDC allowed Positive, Negative, GND Terminals |
Current Load |
24 VDC nominal @ 300 mA |
Operating Temperature |
-25°C to 70°C (-13°F to 158°F) |
Storage Temperature |
-40°C to 80°C (-40°F to 176°F) |
Relative Humidity |
5% to 95% RH with no condensation |
Dimensions (H x W x D) |
5.38 x 1.99 x 4.38 in |
ODVA EtherNet/IP - Declaration of Conformity | 183,48 kB | Dernière Modification 09/11/2020 |
Korean KC Registration | 974,32 kB | Dernière Modification 07/07/2020 |
ATEX Letter of Conformity | 107,32 kB | Dernière Modification 12/05/2022 |
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) | 1,92 MB | Dernière Modification 10/07/2020 |
Declaration of Conformity (RoHS/CE) | 114,24 kB | Dernière Modification 01/06/2022 |
Declaration of REACH Compliance | 145,49 kB | Dernière Modification 01/06/2022 |