PLX32-EIP-104

EtherNet/IP to IEC 60870-5-104 Gateway

PLX32-EIP-104

Integration of EtherNet/IP products into IEC 60870-5-104 networks can be a challenge, but not with ProSoft Technology’s PLX32-EIP-104 gateway.

The gateway has dual Ethernet ports, providing the option to have one Ethernet port communicating on both EtherNet/IP™ and IEC 60870-5-104 networks, or independent communication ports for each protocol.

The gateway provides powerful communications on EtherNet/IP networks, operating as either a Client or a Server to various devices such as PLC’s, Drives, and various other equipment supporting the EtherNet/IP protocol.

On the IEC 60870-5-104 side of the communications, the gateway operates as a server, accepting commands from client devices such as a SCADA system or DCS system.

Images

Click on image(s) to enlarge
Drag with the mouse. Click for close.
Drag with the mouse. Click for close.

Caractéristiques Avantages

  • Up to 10,000 words of user-defined memory to share data between IEC 60870-5-104 and EtherNet/IP networks
  • Up to 1000 points of each supported ASDU type can be exchanged on the IEC-60870-5-104 network
  • EtherNet/IP support as both Client (Class 3 PCCC or CIP) and Server (Class 1 I/O, Class 3 PCCC or CIP)
  • Ability to operate using one Ethernet port, or 2 individual Ethernet ports
  • Upload, Download, Diagnostics via ProSoft Configuration Builder (PCB) via an Ethernet connection
  • Configurable Common ASDU address (sector) and Information Object Address for IEC 60870-5-104 application
  • Optional support for SD card for configuration storage (Sold separately)

Spécifications

EtherNet/IP™ Specifications 

Specification

Description

Number of Class 3 Server Connections

5

Supported Message Types

PCCC and CIP

Number of Class 3 Client Connections

Connected: 2

Unconnected: 1

Number of Class 1 I/O Connections

8

I/O Connection Sizes

248/248

Minimum RPI Time

5mSec per connection

CIP Services Supported

0x4C:CIP Data Table Read
0x4D:CIP Data Table Write
CIP Generic

Command List

Support for 100 commands (Class 3 MSG) per Client

Command Sets

PLC-2/PLC-3/PLC5/SLC500

 

IEC 60870-5-104 Server 

Specification

Description

Operating Mode

IEC 60870-5-104 Server

Simultaneous Connections

3

Unsolicited Messaging

Either cyclic or spontaneous

Group Interrogation

Global, General 1 to 16, Global Counters, Counters 1 to 4

Supported ASDU types

Up to a maximum of 1000 of each of the following ASDU types are supported: M_SP_NA, M_DP_NA, M_ST_NA, M_ME_NA, M_ME_NB, M_ME_NC, M_IT_NA, C_SC_NA, C_DC_NA, C_RC_NA, C_SE_NA, C_SE_NB, C_SE_NC

Matériel

Power Supply

24 VDC nominal
10 to 36 VDC allowed
Positive, Negative, GND Terminals

Current Load

24 VDC nominal @ 300 mA
10 to 36 VDC @ 610 mA maximum

Operating Temperature

-25°C to 70°C (-13°F to 158°F)

Storage Temperature

-40°C to 80°C (-40°F to 176°F)

Humidity

IEC 60068-30; 5% to 95%, with no condensation

Shock

IEC 60068-2-27; 15G @ 11ms (Operational)
IEC 60068-2-27; 30G @ 11ms (Non-Operational)

Vibration

IEC 60068-2-6; 5G @ 10 to 150 Hz

Dimensions (H x W x D)

5.38 x 1.99 x 4.38 in
13.67 x 5.05 x 11.13 cm

Ethernet Port

(2) 10/100 Base-T, RJ45 connector

SD Card

(Optional) Maximum supported size 32GB (located at back of gateway)

Certifications

ATEX Letter of Conformity 107,32 kB Dernière Modification 12/05/2022
CB Safety 348,30 kB Dernière Modification 20/10/2022
Korean KC Registration 974,32 kB Dernière Modification 07/07/2020
UL Certificate of Compliance 233,35 kB Dernière Modification 16/11/2022
Country Approval - Australia 192,66 kB Dernière Modification 07/10/2020
Country Approval - Eurasian Customs Union Conformity (EAC) (Wired) 1,92 MB Dernière Modification 10/07/2020
Declaration of Conformity (RoHS/CE) 114,24 kB Dernière Modification 01/06/2022
Declaration of REACH Compliance 145,49 kB Dernière Modification 01/06/2022