• English
  • 中文
  • Français
  • Deutsch
  • Español
Contact Us
Home
Email
Follow Prosoft Technology on Twitter
Follow Prosoft Technology on Facebook
Follow Prosoft Technology on LinkedIn
Follow Prosoft Technology on YouTube
    • PROFINET Controller Module for ControlLogix®
    • EtherNet/IP™ to DH+ Gateway
    • Two-Port Building Automation Gateway
  • Solutions
    • Amusement
    • Automated Material Handling
    • Automotive
    • IIoT Solutions
    • Mining and Metals
    • Modernization
    • Oil and Gas Solutions
    • Secure Remote Connectivity
    • Water & Wastewater
  • Produits
    • Accès à distance
    • Solutions Rockwell Automation en châssis
    • Passerelles Autonomes
    • Sans fil industriel
    • Logiciels ProSoft
  • SERVICES ET SUPPORT
    • Knowledge Base
    • Support Technique Local
    • Téléchargements
    • Formation
    • Return Material Instructions
    • Documentation
  • ACTUALITÉS
    • ProSoft Insights (Blog)
    • Podcast
      Find a Distributor Request Pricing
      DNRB_Render

      DeviceNet Router/B

      A-DNTR/B

      The DeviceNet Router/B provides a powerful and easy to configure solution to exchange data between DeviceNet™ and EtherNet/IP™, Modbus TCP/IP or Modbus RTU networks.

      The module can be configured as a DeviceNet Scanner or a DeviceNet Device - allowing the user to not only integrate DeviceNet devices into a Logix or Modbus system, it also allows EtherNet/IP or Modbus devices in an existing DeviceNet network.

      The DeviceNet Router B is configured using the Slate Configuration Utility software tool. 

      The DeviceNet Router B includes a web server to display DeviceNet operation and communication statistics and advanced diagnostics functions like built-in packet capture for the various protocols. The router has two Ethernet ports to support Device-Level-Ring (DLR) architectures

      • Images
      • Caractéristiques Avantages
      • Configuration
      • Spécifications
      • Matériel
      • Téléchargements
      • Certifications

      Images

      Click on image(s) to enlarge
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.
      Drag with the mouse. Click for close.

      Caractéristiques Avantages

      • DeviceNet Scanner or DeviceNet Device
      • Support for multiple DeviceNet network baud rates (125K, 250K, 500K)
      • Support for DeviceNet pass-through or explicit messaging
      • PCCC client mode to connect to Ethernet-only PanelViews to an existing DeviceNet network
      • EtherNet/IP Target or Originator with support for Class 1 connections
      • Supports Modbus TCP/IP (Ethernet) and Modbus RTU (Serial) Client/Server
      • Direct-to-Tag Technology
      • Dual Ethernet ports with support for DLR (Device Level Ring)
      • Support for NTP (Network Time Protocol) for external clock synchronization
      • Advanced Diagnostics, including packet capture

      Configuration

      The Slate Configuration Utility software is used for the configuration and troubleshooting of the module. The stand-alone configuration utility allows users to define the setup and configuration of the DeviceNet Router module, connections with controllers and devices.

      Spécifications

      DeviceNet Network 

      Specification

      Description

      Connector

      5-way terminal, 5.08 mm pitch.

      Modes

      Scanner, Target (or Device)

      Baud Rate

      125k, 250k, 500k

      DeviceNet Terminator

      120 Ω (Software enabled)

      DeviceNet Scanner

      Specification

      Description

      Device Count

      63

      Set Target Device Node

      Supported

      Set Target Device Baud Rate

      Supported

      Device Discovery

      Supported

      Explicit Messaging

      Supported

      Supported Connections

      Poll, Change of State (COS)

      DeviceNet Target

      Specification

      Description

      Supported Connections

      Poll, Change of State (COS)

      Input / Output Data Max

      256 bytes input or output, per message

      PCCC Network

      Specification

      Description

      Max PCCC Connections

      10

      Max PCCC Payload

      1000 bytes

      EtherNet/IP Network

      Specification

      Description

      Connector

      RJ45

      Conductors

      CAT5 STP/UTP

      ARP Connections

      Max 100

      TCP Connections

      Max 100

      CIP Connections

      Max 15

      Communication Rate

      10/100 Mbps

      Duplex Mode

      Full / Half

      Auto-MDIX Support

      Yes

      Embedded switch

      Yes, 2 x Ethernet ports

      Device Level Ring (DLR)

      Yes

      Network Time Protocol (NTP)

      Yes

       

      EtherNet/IP Originator

      Specification

      Description

      Class 1 Cyclic Connections Supported

      Yes

      Class 3 / UCMM Connections Supported

      Yes

      Class 1 connection count

      10

      Class 3 / UCMM Target Device Count

      10

      Class 3 / UCMM Mapping Count

      50

       

      EtherNet/IP Target

      Specification

      Description

      Class 1 Cyclic connection count

      4

      Logix Direct-To-Tag supported

      Yes

       

      Modbus Client

      Specification

      Description

      Modes

      Modbus TCP/IP, Modbus RTU (RS232 and 485)

      Modbus RS485 Termination

      125 Ω (Software enabled)

      Maximum Modbus Server Devices

      20

      Maximum Modbus Registers mapped

      100

      Modbus address Range supported

      0 to 65535 of each type (Holding/Input Register, Input/Coil Status)

      Base Offset

      Modbus (Base 0) ; PLC (Base 1)

      Configurable Modbus TCP port

      Yes

      Data Reformatting Supported

      BB AA

      BB AA DD CC

      CC DD AA BB

      DD CC BB AA

       Modbus Server

      Specification

      Description

      Modes

      Modbus TCP/IP, Modbus RTU (232 and 485)

      Modbus RS485 Termination

      Software set

      Modbus address Range supported

      0 to 65535 of each type (Holding/Input Register, Input/Coil Status)

      Base Offset

      Modbus (Base 0) ; PLC (Base 1)

      Configurable Modbus TCP/IP port

      Yes

      Serial Port (RS232)

      Specification

      Description

      RS232 Connector

      9-way terminal (shared with RS485)

      RS232 Conductor

      24 – 18 AWG

      Electrical Isolation

      1000 VDC

      Baud Rates

      1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

      Parity/Data Bits/Stop Bits

      None, Even, Odd / 8 / 1

       Serial Port (RS485)

      Specification

      Description

      RS232 Connector

      9-way terminal (shared with RS485)

      RS232 Conductor

      24 – 18 AWG

      Electrical Isolation

      1500 Vrms (1 minute, maximum)

      Baud Rates

      1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

      Parity/Data Bits/Stop Bits

      None, Even, Odd / 8 / 1

      Matériel

      Specification

      Description

      Power Supply

      Input: 10 to 32 VDC, (85 mA @ 24 VDC and 180mA @ 10 VDC)

      Power Consumption

      2.2 W

      Dimensions

      149.0 x 34.0 x 116.0 mm (H x W x D)

      Connector

      3-way terminal

      Conductors

      24 to 18 AWG

      Enclosure Rating

      IP20, NEMA/UL Open Type

      Temperature

      -20 to 70 °C

      Humidity

      0 to 95% RH, non-condensing

      Earth Connection

      Yes, terminal based

      Emissions

      IEC61000-6-4

      ESD Immunity

      EN 61000-4-2

      Radiated RF Immunity

      IEC 61000-4-3

      EFT/B Immunity

      IEC 61000-4-4

      Surge Immunity

      IEC 61000-4-5

      Conducted RF Immunity

      IEC 61000-4-6

      Téléchargements

      DeviceNet Router/B Datasheet 418,23 kB Dernière Modification 23/11/2023
      DeviceNet Router/B Quick Start Guide 236,47 kB Dernière Modification 06/03/2023
      DeviceNet Router/B User Manual 6,43 MB Dernière Modification 16/04/2026
      DeviceNet Router/B Firmware v1.1.10 187,49 kB Dernière Modification 16/04/2026
      DeviceNet Router/B Release Notes 303,20 kB Dernière Modification 16/04/2026
      DeviceNet Router/B Example 2,55 kB Dernière Modification 06/03/2023
      DeviceNet Router/B EDS Files 3,68 kB Dernière Modification 06/03/2023
      DeviceNet Router/B Dimension Drawings (STEP) 3,92 MB Dernière Modification 23/07/2024
      Slate Software v1.089 87,94 MB Dernière Modification 05/12/2025

      Certifications

      UL/cUL; Class1, Div 2 238,99 kB Dernière Modification 25/01/2024
      CE Declaration of Conformity (CE, UKCA, RoHS, UL) 924,07 kB Dernière Modification 18/07/2025
      ATEX Letter Of Conformity 101,09 kB Dernière Modification 13/10/2023

Solutions

  • Amusement
  • Automated Material Handling
  • Automotive
  • IIoT Solutions
  • Mining and Metals
  • Modernization
  • Oil and Gas Solutions
  • Secure Remote Connectivity
  • Water & Wastewater