The HART Analog Input Gateway provides a clean way to integrate HART Analog instruments with existing controller platforms on an EtherNet/IP network. The gateway works well for field applications where it can be installed closer to HART instrument, saving on copper cable and installation costs. The gateway also saves valuable rack space for other in-chassis options. The gateways provide extremely fast channel update times (all channels updating simultaneously in 67 ms) making the HART Analog Input Gateway ideal for applications where high speeds and point-to-point connectivity are required. These gateways are available in 4 and 8 Analog input channel options.
Rockwell Automation equipment that supports EPIC:
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files and view module and network diagnostics. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects. EtherNet/IP (Explicit Messaging) Compatible Devices Rockwell Automation equipment that supports EPIC:
The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.
The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.
The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.
This area is used to store error codes, counters, and port status information for each port.
This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.
Specification | Description |
Power Supply Input |
24 VDC nominal |
Current Load |
1-4 ch: 190 mA max @ 32 VDC max |
Operating Temperature | -4° F to 122° F (-20° C to 50° C) |
Storage Temperature | -40° F to 185° F (-40° C to 85° C) |
Relative Humidity | 5% to 95% (without condensation) |
Dimensions |
Standard: |
LED Indicators |
Power and Module Status |
Configuration Serial Port |
DB-9M RS-232 only |
HART Interface |
Four (5x08) or eight (5x28) HART Point-to-Point Analog Input channels |
Electrical Isolation | 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991 |
Common Mode Rejection | 105db @ DC |
Over current | ± 40 mA continuous, maximum |
Overvoltage Protection |
All HART Inputs: |
Accuracy | 0.05% of reading @ 25°C for signals between 4 mA to 20 mA |
Built-in 24 VDC loop output power |
1 Internal 24 VDC power supply for each 4 channels. |
Shipped with Each Unit |
Mini-DIN to DB-9M serial cables |
Certifications | CE, cCSAus (Class I, Div 2, Groups ABCD), and ATEX (pending) |
ProSoft Configuration Builder (PCB) | ||
DFNT HART Analog Datasheet | 128,91 kB | Dernière Modification 07/11/2013 |
DFNT Protocol Manual | 2,03 MB | Dernière Modification 24/07/2013 |
HART Analog Protocol Manual | 663,68 kB | Dernière Modification 16/02/2012 |
PLX EDS File | 333,95 kB | Dernière Modification 10/05/2010 |
The EtherNet/IP protocol driver supports the Explicit Messaging implementation of the protocol. User-configurable as both a Client and a Server, the EtherNet/IP port is a very powerful data transfer tool.
The EtherNet/IP protocol is one of the primary connectivity tools to the different Rockwell Automation platforms. The Explicit Messaging aspect of the protocol (only) has been implemented in the ProLinx units to provide the data transfer link between the ProLinx units and the Rockwell Automation hardware.
General Protocol Information |
|
Messaging |
PCCC on CIP |
Miscellaneous |
125 word read and write data lengths |
EtherNet/IP Server Specifications
In Server mode, the module accepts commands from one or more clients to read/write data stored in the module's internal registers.
EtherNet/IP Server Specifications |
|
Connections | Five independent TCP server sockets permit remote clients to interact with all data contained in the module. |
Data File |
Data Table File Start - Fixed at N10 |
CIP Services Supported |
0x4C - CIP Data Table Read |
EtherNet/IP Client Specifications
In Client mode, the module controls the read/write data transfer between the gateway and other EtherNet/IP devices. Data transfer can be initiated and executed without any ladder programming being required in the Rockwell Automation hardware.
EtherNet/IP Client Specifications |
|
General | One client |
Command List | Support for 100 commands, each configurable for command, IP address, register to/from addressing and word/bit count. |
Polling of command list | User configurable polling of commands, including disabled, continuous and on change of data (write only). |
List of Rockwell Automation material that support EPIC:
The HART Analog protocol driver works as a single current loop, point-to-point Master on four channels (all channels set up as channel 0). Each channel is individually configurable.
The auto-poll mode allows the module to automatically collect data from each HART instrument on the channel and store the data in the module's database without the use of user commands. The module automatically generates HART commands 0, 3, 13, 14 and 15.
General Parameters |
|
Communication parameters |
Number of HART Preambles: 2 to 50 |
Configurable Parameters per Channel |
Auto-Poll Enable, Short / Long Address Retries, Retries After Error |
HART Driver |
|
Command List | Up to 100 fully configurable commands per channel |
Polling of command list | User configurable polling of commands, including disabled, continuous, on change of data (write only) and dynamically user or automatic enabled. |
Isolated HART Analog Input Specifications |
|
Input Range | Current: 4 to 20mA with HART |
Resolution | 16bits |
Input Filter | First Order Sync: 10 Hz |
Current Input Resistance | 247.6 ohms +/- 1% |
Open circuit detection time | 1/2 second maximum |
Over current | +/-40mA continuous, maximum |
Common Mode Noise Rejection | 105dB |
Calibrated Accuracy @ 25°C | 4 to 20 mA: 0.05% of reading |
Input Isolation Voltage | 2500 V RMS per UL 1577, transformer isolated |
24V DC Isolation Voltage | 1500 VDC |
HART® is a registered trademark of the HART Communication Foundation
Ex Certificate (ATEX Directive) | 114,27 kB | Dernière Modification 11/11/2013 |
CB Safety | 35,78 kB | Dernière Modification 27/08/2012 |
Declaration of Conformity (RoHS/CE) | 301,03 kB | Dernière Modification 04/03/2018 |
Russian GOST-R | 7,07 MB | Dernière Modification 22/02/2013 |
GOST-R Declaration of Conformity | 6,68 MB | Dernière Modification 22/02/2013 |
UL/cUL; Class 1, Div 2 | 1,08 MB | Dernière Modification 02/07/2013 |
UL/cUL; Class 1, Div 2 (Canada) | 1,10 MB | Dernière Modification 02/07/2013 |